Description
Warranty | 1 Year (UPS), 12 Months (Battery) |
Frequency | Voltage stability: ± 1% (Steady state), ± 5% (Transient state) Transient recovery time: 20 milliseconds to 1% Frequncy stability : ± 0.1% (synchronized with internal clock), ±6% (max) (syncchronized with bypass) Overload capability: 101-110%,60minutes;125-150%,1 minute Voltage distortion with linear load: <1% Voltage distortion with 100% non- linear load: <5% permissible load unbalance: 100% Non linear load capability: 100% Load handling capability without kVA derating: 0.5 lagging to 0.9 leading |
General | General and safety requirements for UPS: IEC 62040-1-1 EMC requirements for UPS: IEC 62040-2 Design & Test Methods (1999): IEC 62040-3 |
Phase angle displacement accuracy | 100% balance load: ±1° 100% unbalanced load: ±1° Isolation Transformer: Built-in |
Input | Nominal input voltage: 380/400/415Vac 3-wire plus Ground Input Voltage Range: 290 to 498 Vac Nominal input frequency: 50/60HZ Input frequency range: 45-55HZ/55-65HZ Input current distortion With: 5% With optional filter Power factor (with filter): 0.9 with optional filter |
Battery | Battery Brand: LEOCH/Equivalent Battery capacity: 12 V,120 AH Number of Battery: 68(34ll34) BCB: 630AH Back Up time: Standard Backup |
Output | Nominal output voltage: 380/400/415Vac 3- phase with Neutral |
Basic Information | Brand: VERTIV Model: Hipulse U Country of origin: USA Country of manufacture: India Nominal Rating: 200 KVA/180KW Rectifier type: 6p |
Physical | Depth (mm): 855 Width(mm): 1240 Height(mm): 1900 Weight (kg): 1200 Kg |